Your items have been reviewed for compliance with the Nebraska State Fire Marshal Act.
Final Architectural Plan New Building
REMARKS:
Code review applies to a Group III aircraft hanger.
1. Open -bay hangars capable of housing multiple aircraft shall be provided with floor drainage in
accordance with Section 5.11. NFPA 409, 8.1.5.1
2. Grounding facilities shall be provided for removal and control of static electrical accumulations on
aircraft while aircraft are stored or are undergoing servicing in a hangar. NFPA 409, 8.7.1
3. An adequate number of floor - grounding receptacles shall be provided. The receptacles shall be either
grounded through individual driven electrodes or electrically bonded together in a grid system and the
entire system grounded to underground metal piping or driven electrodes. Where driven electrodes are
used, they shall consist of 15.9 mm ( in.) diameter or larger metal rods driven at least 1.5 m (5 ft) into the
ground. Floor- grounding receptacles shall be designed to minimize the tripping hazard. NFPA 409, 8.7.2
4. Egress doors for personnel that do not require the opening of doors accommodating aircraft shall be
provided in each partitioned space. Intervals between doors shall not exceed (150 ft) on all exterior walls
or (100 ft) along interior walls. NFPA 409, 8.8.1.1
5. Exit signage shall be provided. LSC 42.2.10
6. Interior wall and ceiling finish material shall have not less than a Class C flame spread rating. LSC
42.3.3.2
This code review does not determine compliance with the State of Nebraska Accessibility Guidelines.
This determination shall be done by the local jurisdiction in which the project is
located.
Page 1 of 2
PLEASE CONTACT OFFICE INDICATED BELOW FOR A FINAL INSPECTION.
FINAL O ITE PROVAL IS REQUIRED PRIOR TO OCCUPANCY OR USE.
Jim Kenney
SIGNED:
Reviewed By: Main Office Contact for Inspection: District B
246 South 14th Street 438 W Market
Albion NE 68620 -1241
Lincoln, NE 68508 -1804 (402) 395 -2164
(402) 471 -2027
i
i
11121/2012 M 11072 -12
i
Mel Morton
Lacey Construction, Inc. Blair Municipal Airport Hanger
i
4601 S. 50th Street, Suite 213 2785 State Hwy 133
Omaha, NE 68117- Blair 68008- j
(402) 905 -2700
i
Your items have been reviewed for compliance with the Nebraska State Fire Marshal Act.
roe • • e • o• • e • 'e
i
i
I
Final Architectural Plan New Building WSJ
CC, District B
l
i
Email: meace inc.com
Alt Phone: � Y
Occupancy Type: Storage Construction Type: IIB 7200 SF
Estimated Start Date: 11/19/2012 Estimated Completion Date: 1/25/2013
Fire Protection Features: j
i
Sprinkler Total ❑ Spinkler Partial ❑ Range Hood System❑ Sprinkler Other:
Fire Alarm Manual Sys. ❑ Smoke Detection ❑ Heat Detection ❑ Fire Alarm Other:
Page 2 of 2
PLEASE CONTACT OFFICE INDICATED BELOW FOR A FINAL INSPECTION.
FINAL O ITE 1EPROVAL IS REQUIRED PRIOR TO OCCUPANCY OR USE.