ps-2011-00075_0003 (2).jpg C -9984 Fapio NRD Blair Office B1 Drawing Date:3 -14 -I1 3116111` 14:27
HYDRAULIC DESIGN INFORMATION SHEET
RECEIVE'
Job Name: C -9984 Papio NRD Blair Office B1
Location: 1060 Wilbur APR 0 2011
Blair, NE 68008
Drawing Date: 3 -14 -11 Remote Area Nu ()FIBLAIR
Contractor: Continental Fire Sprinkler Co. Telephone:(402)3NE99& *'
4518 South 133rd Street
Omaha, Nebraska, 68137 i
Designer: Eric Caudillo
Calculated By:SprinkCAD
www.sprinkcad.com FILE h -,,
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: Steel /Wood Occupancy:Office Building
Reviewing Authorities:State
SYSTEM DESIGN
i
Code:NFPA 13 Hazard:LIGHT System Type:WET
I
Area of Sprinkler Oper. 1500 sq ft► Sprinkler or Nozzle
Density (gpm /sq ft) 0.100 I Make: VIKING
Area per Sprinkler 230.0 sq ft] Model: M VK302
Hose Allowance Inside 0 gpm I K- Factor: 5.60
Hose Allowance Outside 100 gpm I Temperature Rating: 155
CALCULATION SUMMARY 11 Flowing Outlets
gpm Required: 353.6 psi Required: 80.2 @ Source
WATER SUPPLY
Water Flow Test I Pump Data
Date of Test 9 -2 -08 I Rated Capacity 0 gpm
Static Pressure 95.0 psi I Rated Pressure 0.0 psi
Residual Pres 70.0 psi I Elevation 0
At a Flow of 1320 gpm I Make:
Elevation 0" Model:
Location: 10th and Wilbur St.
Source of Information: Blair Water Dept.
SYSTEM VOLUME 129 Gallons
Notes: