gT fi NEBRASKA STATE FIRE MARSHAL
PLANS DIVISION N
NFAX
Code Review
412512011 M 04057 -11
Eric Caudillo
CONTINENTAL FIRE SPRINKLER CO, Papio NRD Blair Office Bldg C -9984
4518 S 133rd St 1060 Wilbur
OMAHA, NE 68137 -0777 Blair 68008- L N -)- o 10- 6 0! 6 I
Your items have been reviewed for compliance with the Nebraska State Flre Marshal Act.
; Sprinkler Shop Drawing
REMARKS:
1. Drawing is approved for layout and design,
2. After the systems have been installed, the completed Contractor's Material and Test Certificates for
Aboveground and Underground piping shall be provided to and accepted by the State fire Marshal to
receive final approval. This must be done before the system is put into service. Title 1.53, Chapter 19; Q-
1 03 -06.
I
6 -1118
Page 1 of 1
PLEASE CONTACT OFFICE INDICATED BELOW FOR A FINAL INSPECTION.
FINAL APPROVAL IS REQUIRED PRIOR TO OCCUPANCY OR USE
SIGNED. Jim Kenney
Reviewed By Main Office Contact for Inspection: District B
246 South 14th Street 438 W Market
Lincoln, NE 68508 -1504 Albion NE 68620 -1241
(402) 471 - 2027 (402) 395 -2164