ad-2011-00214_0004.jpg Howard Wolfe
From: Howard Wolfe
Sent: Thursday, June 16, 2011 4:03 PM
To: 'robert.kilpatrick @evonik.com'
Cc: Howard Wolfe
Subject: Envoik 2011 Biolys Expansion- Fermentation Building Addition -CN- 2011 - 00214 -Plan review
comments
Date: 6 -16 -2011
Re: Evonik Biolys Expansion- Fermentation Building Add ition -CN- 2011 -00214
Robert: Please review the following plan review comments and respond.
1. Evonik Code Analysis reads that the number of stories for the new addition are 4. Table 503 allows only 3 stories for
a non sprinklered F -2 occupancy of type II -B construction.
2. Show on the plans fire department access openings as per Section 903.2.11.1.
3. Show a class III Standpipe system as per Section 905.3.1.
4. Provide an exiting plan. Show travel distance from each floor to an exit or exit enclosure.
5. Show on the plans exit enclosures as per Section 1022.
6. Indicate the height, area, #of stories, and type of construction of the administration building.
7. Show on the plans exit sign and exit illumination requirements as per Sections 1011 and 1006.
Thank you,
Howard Wolfe
Building Inspector
City of Blair
218 South 16th Street
Blair, NE 68008
Office: (402) 426 -4191
Direct: (402) 426 -6696
Fax: (402) 426 -4195