ad-2011-00214_0002.jpg ® EvoniK Client: Evonik's Midwest Lysine Plant Project No. P414211505 Project: 2011 Biolys Expansion, Blair, NE Date: May 31, 2011 Revised: June 23, 2011 Building Code Analysis Applicable Codes: 2009 International Building Code NFPA 101 Occupancy Class: F -2: Factory Industrial Low Hazard Occupancy (Sect. 306.3) This occupancy classification is consistent with "F2 —Low Hazard Occupancy" used when the existing fermentation building was first constructed under the 1997 Uniform Building Code in 1999. The following code criteria were noted on the architectural cover sheet of the original construction drawings dated 4 -07- 1999: • All work to be done in accordance with 1997 Uniform Building Code, OSHA latest edition, all applicable local codes and ordinances. • Occupancy: Use Group "F -2" — Low Hazard Occupancy • Construction Type: Type II — Non — protected • Allowable Floor Areas: 36,000 sf. /floor • Allowable Heights: 55' with variances granted for main building and high bay • Travel Distance: 300' for non - sprinklered building Per section 307.1 High Hazard Group H — Exception 5, Closed piping containing flammable or combustible liquids or gases utilized for the operation of machinery or equipment shall not be classified in Group H, but shall be classified in the occupancy that they most nearly resemble. Floor Area: Existing Building Area 1: (unsprinklered) 32,500 sf `\O WkL C Proposed Addition Area: (unsprinklered) 6,750 sf �.• .Fy Total Area: 39,250 sf ' C o; JAMES F .e Number of Stories: 1 story with multi -level equipment platforms (Revised: June 23, 2011) L: KELLEY ; M • E - 13243 Building Height: 100' -0" (Matches Existing). No change to existing building height. ct'J•. `�3 /ZviQ Height and Area Limitation (per IBC Table 503): � NE�� Based on Type II B Construction (existing and proposed construction type): F -2: Height limitation — 3 story (55' /story), Area limitation — 23,000 sf Per section 503.1.1: Special industrial occupancies. Buildings and structures designed to house special industrial processes that require large areas and unusual building heights to accommodate crane ways or special machinery and equipment including, among others, rolling mills; structural metal fabrication shops and foundries; or the production and distribution of electric, gas or steam power, shall be exempt from the building height and area limitation of Table 503. Since the existing fermentation structure and the proposed fermentation addition are used to house fermentation and evaporation processes and is a normally unoccupied equipment enclosure as opposed to an occupied building, we believe that the structure could be categorized as a special industrial occupancy in accordance with Section 503. 1.1 and should be exempted from the height and area limitation of Table 503. Page 1 of 2