2267 Nebraska StJanuary 13, 2011
OWNER(S) OF RECORD:
Henry R. Gregory Revocable Trust
2068 Nebraska Street
Blair, NE 68008
City of Blair
218 S. 16th Street
Blair, Nebraska 68008
(402) 426-4191
FAX (402) 426 4195
Email: cityofblair@ci.blair.ne.us
LEGAL DESCRIPTION: Inspection Request for 2267 Nebraska Street, Blair, Nebraska
Lot 7 and Part of vacated Street, Block 4, Dexter's First Addition, Blair City,
Washington County, NE
Dear Mr. Gregory,
On December 1, 2010, the undersigned Code Official of the City of Blair, Nebraska, hereby determined that the
residential structure on the above described property is in violation of the 2009 International Property
Maintenance Code, as adopted by the City of Blair, Nebraska.
A structure is considered unsafe if found to be dangerous to the life, health, property or safety of the public or
occupants, if the structure contains unsafe equipment or is so damaged, decayed, dilapidated, structurally
unsafe, or of such faulty construction or unstable foundation, that partial or complete collapse is likely. Unsafe
Equipment shall include any boiler, heating equipment, elevator, moving stairway, electrical wiring or device,
flammable liquid containers or other equipment on the premise or within the structure which is in such disrepair
or condition that such equipment is a hazard to life, health, property or safety of the public or occupants of the
premises or structure. Structures are unfit for human occupancy whenever the code official determines that a
structure is unsafe, unlawful or because of the degree to which the structure is in disrepair or lacks maintenance,
is unsanitary, infested, contains filth and contamination, or lacks ventilation, illumination, sanitary or heating
facilities or other essential equipment required by the code or because of the location of the structure constitutes
a hazard to the occupants of the structure or to the public. Unlawful structure is one found in whole or in part
to be occupied by more persons than permitted under this code, or was erected, altered or occupied contrary to
the law.
IT IS THEREFORE ORDERED, by the Code Official of the City of Blair, Nebraska that the owner(s)
of record, as shown by the real estate records of Washington County, being:
Henry R. Gregory Revocable Trust
2068 Nebraska Street
Blair, NE 68008
of the above described premises, must repair, alter, remove, or demolish and disposed of properly, said
dwelling, dwelling unity, structure, building, wall and/or equipment, or shall otherwise cause to correct the
conditions which make the building or structure in violation of the 2009 International Property Maintenance
Code, as outlined in the attached inspection report, on or before March 14, 2011. Failure to correct all of the
deficiencies identified in the inspection report on or before the compliance deadline will result in a $300
inspection fee assessment against the property owner.
If the recipient believes this compliance order or the contents of the attached inspection report were prepared
in error or do not accurately reflect the current conditions of the property, a hearing may be requested before
the City Administrator or his designated agent to give testimony and show cause why this order should not be
issued against the property owner.
CITY OF BLAIR NEBRASKA
BY: fir/ 'L%
Howard Wolfe, Building/Code Inspector
April 22, 2011
Rodney Storm
City Administrator
218 South 16th Street
Blair, NE 68008
RE: 2267 Nebraska Street, Blair, Nebraska
Dear Mr. Storm:
In your letter dated February 2nd, 2011 you said to contact you again if all work on 2267 Nebraska
Street would not be completed by June 1st, 2011.
I will be returning to Blair on May 19th or 20th. Decisions on final decorating will not be made until my
return.
As I have mentioned in the past, the house will not be rented until all work is done and it has been
inspected by Howard Wolfe.
Your continued cooperation would be welcome.
Sincerely,
Henry R. Gregory
2421 South Conway
Mission, TX 78572
11*0
ase 01
February 2, 2011
CITY Of t)LAIQ
OWNER (S) OF RECORD: (As Identified from the Washington County Assessor's Office)
Henry R. Gregory, H Revocable Trust
2124 S. Conway
Mission, TX 78572
RE: 2267 Nebraska Street, Blair, Nebraska
Lot 7 and Part of vacated Street, Block 4, Dexter's First Addition, Blair City,
Washington County, NE
Dear Mr. Gregory,
We are in receipt of your letter dated January 27, 2011 regarding the above property and would
like to thank you for your willingness and cooperation in working with the City of Blair to
resolve the issues at this location.
As requested, we will grant you an extension until June 1, 2011 to complete the items that have
been previously outlined to you on the property maintenance inspection report. However, as a
reminder, until such time a Final Inspection is made by Howard Wolfe, City Building Inspector,
NO occupancy of the residence is allowed. If you need additional time beyond this date, feel free
to contact me again.
Again, thank you for your cooperation in this matter. Feel free to contact me again if you have
any additional questions.
,
m
I
�1
City Administrator
'=
EOEOUIL- HOUPI G
OPPORTUNITY
218 South 16th Street • Blair, Nebraska 68008 • 402-426-4191 • Fax 402-426-4195 • E-mail cityofblalr@d,blalr,ne.us
January 27, 2011
Howard Wolfe
Building Code Inspector
City of Blair
218S.16 1h Street
Blair, Ne 68008
Cc: City Administrator
City of Blair
218 S. 16th
Blair, NE 68008
Jack Bennett
2016 Wright Street
Blair, NE 68008
Re: 2267 Nebraska Street
Blair, NE 68008
Dear Sirs:
I am in receipt of your letter of January 13th, 2011 which documents violations of the 2009 International
Property Maintenance Code. As I told Mr. Wolfe via telephone, I agree that the structure is currently
unfit for human occupancy. I evicted the tenants who caused it to be in this condition on November
15th, 2010.
After the tenants had been displaced by court order on November 15th, 2010,1 went to Texas for health
reasons and will spend the winter here.
My property representative, Jack Bennett has been overseeing the reconstruction of the property at
2267 Nebraska Street. This will be a laborious and costly reconstruction due to the willful and extensive
destruction of the property by the evictees. In addition to said destruction, dog feces and the stink of
dog urine virtually covered every inch of the flooring in the house.
My initial emotional response to your letter is that you are blaming the victim, as I surely am in this case.
In violation of their lease, the tenants changed the locks and refused me admittance so I could check on
the condition of the house. Therefore, I was not aware of the extensive damage until after the eviction
when my representative advised me and sent pictures of the conditions.
In addition, possibly due to their refusal to pay rent, the tenants did not notify me of any mechanical
problems.
I do not have documentation of the final electrical approval by your office. However, my electrical
contractor, John Duggan of Duggan Electric worked with your office and the rewiring was inspected and
approved.
Repairs have been ongoing since November 15th, 2010 and many of the issues have been resolved.
However, I do not believe it will be possible to correct all deficiencies by March 14th, 2011, as my
contractor has given me an estimate of thirty thousand dollars for proper restoration of the property.
In light of the above, I beg your forbearance and a more reasonable time period for compliance. As
health care issues preclude my return to Blair until the third week of May 2011,1 will be unable to make
the final repairs until my own visual inspection.
The structure will be in a safe and habitable condition at the earliest possible date. I assure you, the
property will not be occupied until the repairs have been made and the property brought up to code.
Respectfully Yours,
Henry R. Gregory, Trustee
The Henry R. regory, II Revocabl Trust
�r �'����
P. S. S Id yo want to reac me by telephon , my cell number is 402-321-6268. My Texas address is
2124 S. Conway, Mission, TX 78572.
dr! rr ill
NO
r1 'r
K
'" ��� e } �� SRT' rR'", i� y-�•.• _' `�j � �- "''.I � -- ._
I;i}ji�y+
� -� 1��� .- ,` ,• �"A,'♦1^'�',�• ��%•,,,,, � t r.'� a y .. :•�
,� se..,�►' ' ,* ' •iii :�'>5 •• .Pa 0'��,$� 1
•40
d' q r ✓
+. it 1.r% a •. \� 14+'
"' ��. 'ti• J .ir
ri4p-$•q • .yam, ,!� 11 W ¢
w'M a�� F.. '11 � t�.�vr 1 '�� ids a* � � ,; `��J14 9 � +•,+
:.- .• x.., a r{. ��1� t . ?r ++� p „•,�Jf yl-`.. � _r , 3 � `�'��Ytit'�� -� -aW.
,�. �arr '�� Aro ^i+6.°�'#�.ti .s „� r at�';� a,.�,�•,� '
r, •'rt• • ,� h �. m dam, �a�':Y' � � , y r �,�r; r+ . w ,�'+..e ^ �•M Jn!•" �
.i*�"-. �,P�.'`�`.• G t �'r 'aq "�7t � ''r� eY ,-� r � r �. r �,`w�:. ��> -•,r � i`rs 7 'i' �Y.e,. r � -
Nta`�e. ,Jhs a IC' ¢ t '�► i�,� r-..'•y�,:.r• .tea � T
*Kt,"°
S SG w•? , s ' py s t . "3` �� r W*
�� nr�'� ni.. � �I ,tll`:L' n.�+•P�x '�'"�'�¢¢y §,. eF R: �J�x a�»_"U'1i� o�-.d'� = .k � - f5'r�`f�'�' '�: �'�-' P (�. �Yyj,
All
�,y'��f• �r ��!"*9,V• •. ..°.,, �.r=�r�. 7��*ACi JP'd�/��tii
y,.... .r / R•p'6•r k d 9r4iT,\i ''�, ". •i' "'�'."..vf►
ug , .,��./ '"./. • � y�y •.. '4:f1 k, -.y `°°"a -e��,i y %.rt . 4' ��i �., � �i'
r n »
r
IL If
� i� �.. �,a5
�9ruY.- "` "^�I r� dl '�'f��� �y_,4 Y •I�� s ° � r , 1" �
� �.` z/��,' �"�`�,'�`'• ,ed♦..�+r�r � •a t..'9t F ��,��A�' �.:' .� � ay � ,t I rr �i'j
.� -. _ .... �� A "'Fi �"� `'air., �` .'���
I F� �
7j �7`,',1�y7 � ,�.,
,t
0
Juu.,n' Lan
R
t
lo
I
A
K.
T!:
f,
l �
l �D,
r
r.H S Ali
..y
1 �
S �
IT .
�, }9? E '1� x4�'',' , `� i ��• +�.+ t w , i�' � r fl y. *�y, � � �L� 5 L Y}ro �+• �+ A` F �+i, . v
Ip
� c r .-edo fi ; , r u 1 Y � �`rr h. , ti� 1 �'� � �7'' 'yr•�1 � )� 4 9�_ c.,
1 a �l�R•,. �r3�? J Ir%h ' any 1, I.., • �-,
ow
t1a' r
�il °' au iFl�t ,+ 1�1 . �' i N� x r �.°;�iR9'✓• k II; yF�� � � i �.�.�ii�� �'• {
a .,I i �} fy.. .r'�b, ^: I°f'�� N I. y.lcf t V� _ � 4•i
a i
1 V
r
6ci rues
L{UZ - %3U- SO 11
be�er�
G�.�-�ns.
(l�'� � ��-e, �.�G. �' ��e � �
Cl c1C door .6la.�e�
o �- � Sh-���4ZLYL -in
I�c�l�5 -k bC, c is b � ''��
kC
to
l�lo,� C) w-�-r-
O
y � A ��.• �
oaf
I� ,'
.
4
4
pp,
'
� 1 t
:'. ^ S
�. �:.�t �� n.1
���
'� '7y` T
,'��:
l�
� �
. �..y�
_?
_,
4 �,�,,((y�
1Vh�
F
I{
NI i Z,
�.}.�
'�7 ���/''7��V 'f �.
� t w�•.
�n J
r l
^W � t
� Y�Y, w
�h �r �, ���r .. "fi
~
M�\^�
I � .� Atj
) 1 r� `
1�
`L
`�-ar- TL i�, .,
��
»... �
t
1
I
F- �'
1 7�1
lip....... . . . . . . . . . .
.M�,
�,..
��*
ir11.�
Y'����
.�
r
� ;,f _, � a � ;:: w
s a if v '.1 a� m�xr � ii )t�'�'"yy>.�«,A�. { �� �" ,y �� _+,r..., �.,a,.�,�,-....,,,,_„
N
"d
v
s
a
x
�
' a
i
v
a
x
�
' a
i
+ i
(
�� �
R
` � � ..II .-. ^`-.�
�!- * � f } J •�r .rr��' "IPS i � , r�.. �,l^,
' q.-
�� '"' � Y!+ r �� { 1 fid' �
•'�` � �t 4/ a11� N � �
V '
• a;
1 ':
i
•
r, r'''ef d � � , �.
o
� ,
i.�: •#
.mfr
*^leL,
�.,° r,Y'ia? y �'�
`•-NO'S -
-. �•., 1.
-�'.
v
'
MIL -
k
a mow,
AL olh i
ygy,,
1 1
e
C.J
-r
61,
¥.
i�
7:QO Parcel & Addre_ s
� Address Location, 94, 201, 323 82,304.218 Feet
nership Parcels
features
Friday, Nov 19, 2010 01:57 PM
Field Value
�lok
BookPage 482-729
CalcArea 0,211587
Dissolve—Shape Polygon
Legal BC DEXTERS 1 ST ADD LOT 7 & PT OF 'QAC ST BLIP 4 114 PC 3
Mail
Mail2 2068 NEBRASKA ST
Mail3 BLAIR, NE
OBJECTID 24313
OBJECTID 1 99323
Owner GREGORY, HENRY R REVOCABLE TRUST
-
OwnID 2090072
ParcelID 890050932
ParcelIdentity 890050932
ParcelType Single Owner Parcel
PID 890050932
Problems
PropClass 1000
PropType RES
Shape _Area 9216,734241
Shape—Length 512,45949
Situs 2267 NEBRASKA ST BLA
TransLevel 0
Zipcode 68008-0000
features
Friday, Nov 19, 2010 01:57 PM
J 2 features
Friday, Nov 19, 2010 02:01 PM
1
from: Parcel & Address
lel & address
Ownership Parcels
_--.._........ _........ ___ _._ _ _ . __ _ .._...._.._........_....--......._..-....
Location: F94, 26 1. 660 $2, 310.252 Feek
Field
'value
T axlots
BookPage
482-730
CalcArea
0,235727
Dissolve_Shape
Polygon
j Legal
BC DEXTERS 1 ST ADD LOT 6 & PT OF VAC ST BLK 4 114 PC 4
Mail
Mail2
2068 NEBRASKA ST
Mail3
BLAIR, NE
OBJECTID
24312
OBJECTID_1
99322
Owner
GREGORY, HENRY R REVOCABLE TRUST
OwnID
2090072
ParcelID
890050925
ParcelIdentiky
890050925
ParcelType
Single Owner Parcel
PID
890050925
Problems
PropClass
1000
PropType
RES
Shape _Area
10268.251811
Shape_Length
462,836998
Situs
2255 NEBRASKA ST BLA
TransLevel
0
2ipcode
68008-0000
J 2 features
Friday, Nov 19, 2010 02:01 PM
City of Blair
Property Maintenance Report
Date: 12-1-2010
Owner Name: Hank Gregory
Property Location: 2267 Nebraska St.
Legal Description:
Violation
Code Description
Comments
M
Chapter 3 — General Requirements
Section 302 Exterior Property Areas
302.01 SANITATION. All exterior property and premises shall be maintained in a
Garbage everywhere, inside and out.
X
clean, safe, and sanitary condition
302.02 GRADING AND DRAINAGE. All premises shall be graded and maintained to
prevent the erosion of soil and to prevent the accumulation of stagnant water thereon, or
within any structure located thereon. Exception: Approved retention areas and
reservoirs.
302.3 SIDEWALK AND DRIVEWAYS. All sidewalks, walkways, stairs, driveways,
and similar areas shall be kept in a proper state of repair, and maintained free from
hazardous conditions.
302.4 WEEDS. All premises and exterior property shall be maintained free from weeds
Weeds need cut around ground level B -vent and a
X
or plant growth in excess of 12 inches.
concrete slab installed around the B vent to prevent
future weeds from contacting the vent.
302.5 RODENT HARBORAGE. All structures and exterior property shall be kept free
from rodent harbarage and infestation. Where rodents are found, prompt extermination
shall be implemented. Precautions for reinfestation required.
302.6 EXHAUST VENTS. Pipes, ducts, conductors, fans or blowers shall not
discharge gases, steam, vapor, hot air, grease, smoke, odors or other gaseous particulate
wastes directly upon abutting public or private property.
302.7 ACCESSORY STRUCTURES. All accessory structures, including detached
garages, fences and walls, shall be maintained structurally sound and in good repair.
302.8 MOTOR VEHICLES. No inoperative or unlicensed motor vehicle shall be
parked, kept or stored on any premises, and no vehicle shall at any time be in a state of
major disassembly, disrepair or in the process of being stripped or dismantled.
302.9 DEFACEMENT OF PROPERTY. No person shall willfully or wantonly damage,
mutilate, or deface any exterior surface of any structure on private or public property by
placing thereon any marking, carving or graffiti.
Section 303 Swimming Pools, Spas and Hot Tubs
303.1 SWIMMING POOLS. Swimming pools shall be maintained in a clean and
sanitary condition.
303.2 ENCLOSURES. Private swimming pools, hot tubs and spas, containing more than
24 inches (6 10 mm) in depth shall be completely surrounded by a fence or barrier at
least 48 inches (1219 mm) in height above the finished ground level measured on the
side of the barrier away from the pool.
Section 304 Exterior Structure
304.1 GENERAL. The exterior of a structure shall be maintained in good repair,
structurally sound and sanitary so as not to pose a threat to the public health, safety or
welfare.
304.2 PROTECTIVE TREATMENT. All exterior surfaces, including, but not limited
to, doors, door and window frames, cornices, porches, trim, balconies, decks and fences
shall be maintained in good condition. Exterior wood surfaces, other than decay -
resistant woods, shall be protected from the elements and decay by painting or other
protective covering or treatment. Peeling, flaking and chipped paint shall be eliminated
and surfaces repainted.
304.3 PREMISES IDENTIFICATION. Buildings shall have approved address numbers
placed in a position to be plainly legible and visible from the street or road fronting the
property.
304.4 STRUCTURAL MEMBERS. All structural members shall be maintained free
from deterioration, and shall be capable of safely supporting the imposed dead and live
loads.
304.5 FOUNDATION WALLS. All foundation walls shall be maintained plumb and
free from open cracks and breaks and shall be kept in such condition so as to prevent the
entry of rodents and other pests.
304.6 EXTERIOR WALLS. All exterior walls shall be free from holes, breaks, and
Needs new paint.
X
loose or rotting materials; and maintained weatherproof and properly surface coated
where required to prevent deterioration.
304.7 ROOFS AND DRAINAGE. The roof and flashing shall be sound, tight, and not
have defects that admit rain. Roof drainage shall be adequate to prevent dampness or
deterioration in the walls or interior portion of the structure. Roof drains, gutters and
downspouts shall be maintained in good repair and free from obstructions. Roof water
shall not be discharged in a manner that creates a public nuisance.
304.8 DECORATIVE FEATURES. All cornices, belt courses, corbels, terra cotta trim,
wall facings and similar decorative features shall be maintained in good repair with
proper anchorage and in a safe condition.
304.9 OVERHANG EXTENSIONS. All overhand extensions, including canopies,
marquees, signs, metal awnings, fire escapes, standpipes and exhaust ducts shall be
maintained in good repair and be properly anchored so as to be kept in sound condition.
304.10 STAIRWAYS, DECKS, PORCHES AND BALCONIES. Every exterior
stairway, deck, porch and balcony, and all appurtenances attached thereto, shall be
maintained structurally sound, in good repair, with proper anchorage and capable of
supporting the imposed loads.
304.11 CHIMNEYS AND TOWERS. All chimneys, cooling towers, smoke stacks and
similar appurtenances shall be maintained structurally safe and sound, and in good
repair. All exposed surfaces of metal or wood shall be protected from the elements and
against decay or rust by periodic application of weather -coating materials, such as paint
or similar surface treatment.
304.12 HANDRAILS AND GUARDS. Every handrail and guard shall be firmly
fastened and capable of supporting normally imposed loads and shall be maintained in
good condition.
304.13 WINDOW, SKYLIGHT AND DOOR FRAMES. Every window, skylight, door
Window sills rotten, needs renewed.
and frame shall be kept in sound condition, good repair and weather tight. All glazing
X
materials shall be maintained free from cracks and holes. Every window, other than a
fixed window, shall be easily openable and capable of being held in position by window
hardware.
304.14 INSECT SCREENS. From May 1 and October 1, every door, window and other
Needs insect screens in good condition on all openable
outside opening required for ventilation of habitable rooms, food preparation areas, food
W1ndOWS.
service areas or any areas where products to be included or utilized in food for human
consumption are processed, manufactured, packaged or stored, shall be supplied with
X.
approved tightly fitting screens of not less than 16 mesh per inch (16 mesh per 25 mm)
and every swinging door shall have a self-closing device in good working condition.
Exceptions: Screens shall not be required where other approved means, such as air
curtains or insect repellent fans, are employed.
304.15 DOORS. All exterior doors, door assemblies and hardware shall be maintained
Renew Or repair exit door. Repair exterior window door
X
in good condition. Locks at all entrances to dwelling units, rooming units and guest
at grade for basement window.
rooms shall tightly secure door.
304.16 BASEMENT HATCHWAYS. Every basement hatchway shall be maintained to
prevent the entrance of rodents, rain and surface drainage water.
304.17 GUARDS FOR BASEMENT WINDOWS. Every basement window that is
openable shall be supplied with rodent shields, storm windows or other approved
protection against the entry of rodents.
304.18 BUILDING SECURITY. Doors, windows or hatchways for dwelling units,
room units or housekeeping units shall be provided with devices designed to provide
security for the occupants and property within.
304.18.1 DOORS. Doors providing access to a dwelling unit, rooming unit or
housekeeping unit that is rented, leased or let shall be equipped with a deadbolt lock
meeting specifications set forth herein. Such deadbolt locks shall be operated only by
the turning of a knob or key and shall have a lock throw of not less than 1 -inch. For the
purpose of this section, a sliding bolt shall not be considered an acceptable deadbolt
lock. Such deadbolt locks shall be installed according to manufacturer's specifications
and maintained in good working order. All deadbolt locks required by this section shall
be designed and installed in such a manner so as to be operable inside of the dwelling
units, rooming unit or housekeeping unit without the use of a key, tool, combination
thereof or any other special knowledge or effort.
304.18.2 WINDOWS. Operable windows located in whole or part within 6 feet (1828
mm) above ground level or a walking surface below that provide access to a dwelling
unit, rooming unit or housekeeping unit that is rented, leased or let shall be equipped
with a window sash locking devices.
304.18.3 BASEMENT HATCHWAYS. Basement hatchways that provide access to a
dwelling unit, rooming unit or housekeeping unit that is rented, leased or let shall be
equipped with devices that secure the units from unauthorized entry.
Section 305 Interior Structure
305.1 GENERAL. The interior of a structure and equipment therein shall be maintained
in good repair, structurally sound and in a sanitary condition. Every OCCUPANT shall
keep that part of the structure he occupies or controls in a clean and sanitary condition.
Every OWNER of a structure containing a rooming house, hotel, dormitory, two or more
dwellings units, shall maintain in a clean and sanitary condition, the shared or public
areas of the structure and the exterior property.
305.2 STRUCTURAL MEMBERS. All structural members shall be maintained
structurally sound, and be capable of supporting the imposed loads.
305.3 INTERIOR SURFACES. All interior surfaces, including windows and doors,
shall be maintained in good, clean and sanitary condition. Peeling, chipping, flaking or
abraded paint shall be repaired, removed or covered. Cracked or loose plaster, decayed
wood and other defective surface conditions shall be corrected.
305.4 STAIRS AND WALKING SURFACES. Every stair, ramp, landing, balcony,
porch, deck or other walking surface shall be maintained in sound condition and good
repair.
305.5 HANDRAILS AND GUARDS. Every handrail and guard shall be firmly fastened
and capable of supporting normally imposed loads and shall be maintained in good
condition.
305.6 INTERIOR DOORS. Every interior door shall fit reasonably well within its frame
and shall be capable of being opened and closed by being properly and securely attached
to jambs, headers or tracks as intended by the manufacturer of the attachment hardware.
Section 306 Handrails and Guardrails
306.1 GENERAL. Every exterior and interior flight of stairs having more than four
risers shall have a handrail on one side of the stair and every open portion of a stair,
landing, balcony, porch, deck, ramp or other walking surface which is more than 30
inches (762 mm) above the floor or grade below shall have guards. Handrails shall not
be less than 30 inches (762 mm) high or more than 42 inches (1067 mm) high measured
vertically above the nosing of the tread or above the finished floor or the landing or
walking surfaces. Guards shall not be less than 30 inches (762 mm) high above the floor
of the landing, balcony, porch, deck or ramp or other walking surfaces. Exception:
Guards shall not be required where exempted by the adopted building code.
Section 307 Rubbish and Garbage
307.1 ACCUMULATION OF RUBBISH OR GARBAGE. All exterior property and
Remove.
X
premises, and the interior of every structure, shall be free from any accumulation of
rubbish or garbage.
307.2 DISPOSAL OF RUBBISH. Every occupant of a structure shall dispose of all
rubbish and garbage in a clean and sanitary manner by placing such rubbish in approved
containers. 307.2.1 RUBBISH STORAGE FACILITIES. The owner of every occupied
premises shall supply approved covered containers for rubbish, and the owner of the
premises shall be responsible for the removal of rubbish. 307.2.2 REFRIGERATORS.
Refrigerators and similar equipment not in operation shall not be discarded, abandoned
or stored on premises without first removing the doors.
307.3 DISPOSAL OF GARBAGE. Every occupant of a structure shall dispose of
garbage in a clean and sanitary manner by placing such garbage in an approved garbage
disposal facility or approved garbage containers. 307.3.1 GARBAGE FACILITIES.
The owner of every dwelling shall supply one of the following: an approved mechanical
food waste grinder in each dwelling unit; an approved incinerator unit in the structure
available to the occupants in each dwelling unit; or an approved leakproof, covered,
outside garbage container. 307.3.2 CONTAINERS. The operator of every establishment
producing garbage shall provide, and at all times cause to be utilized, approved
leakproof containers provided with close -fitting covers for the storage of such materials
until removed from the premises for disposal.
Section 308 Extermination
308.1 INFESTATION. All structures shall be kept free from insect and rodent
infestation. All structures in which insects or rodents are found shall be promptly
exterminated by approved processes that will not be injurious to human health. After
extermination, proper precautions shall be taken to prevent reinfestation.
308.2 OWNER. The OWNER of any structure shall be responsible for extermination
within the structure prior to renting or leasing the structure.
308.3 SINGLE OCCUPANT. The occupant of a one -family dwelling or of a single -
tenant nonresidential structure shall be responsible for extermination on the premises.
308.4 MULTIPLE OCCUPANCY. The owner of a structure containing two or more
dwelling units, a multiple occupancy, a rooming house or a nonresidential structure shall
be responsible for extermination in the public or shared areas of the structure and
exterior property. If infestation is caused by failure of an occupant to prevent such
infestation in the area occupied, the occupant shall be responsible for extermination.
308.5 OCCUPANT. The occupant of any structure shall be responsible for the continued
rodent and pest -free condition of the structure. Exception: Where the infestations are
caused by defects in the structure, the owner shall be responsible for extermination.
Chapter 4 - Light, ventilation and Occupancy Limitations
Section 402 Light
402.1 HABITABLE SPACES. Every habitable space shall have at least one window of
approved size facing directly to the outdoors or to a court. The minimum total glazed
area for every habitable space shall be 8 percent of the floor area of such room.
Wherever walls or other portions of a structure face a window or any room and such
obstructions are located less than 3 feet (914 mm) from the window and extend to a level
above that of the ceiling of the room, such window shall not be deemed to face directly
to the outdoors nor to a court and shall not be included as contributing to the required
minimum total window area for the room. Exception: Where natural light for rooms or
spaces without exterior glazing areas is provided through an adjoining room, the
unobstructed opening to the adjoining room shall be at least 8 percent of the floor area o
the interior room or space, but not less than 25 sq. ft. (2.33m2). The exterior glazing area
shall be based on the total floor area being served.
402.2 COMMON HALLS AND STAIRWAYS. Every common hall and stairway in
residential occupancies, other than in one- and two-family dwellings, shall be lighted at
all times with at least a 60 -watt standard incandescent light bulb for each 200 square feet
(19 m2) of floor area or equivalent illumination, provided that the spacing between
lights shall not be greater than 30 feet (9144 mm).
402.3 OTHER SPACES. All other spaces shall be provided with natural or artificial
light sufficient to permit the maintenance of sanitary conditions, and the safe occupancy
of the space and utilization of the appliances, equipment and fixtures.
Section 403 Ventilation
403.1 HABITABLE SPACES. Every habitable space shall have at least one openable
window. The total openable area of the window in every room shall be equal to at least
45 percent of the minimum glazed area required in Section 402.1 Exception: Where
rooms and spaces without openings to the outdoors are ventilated through an adjoining
room, the unobstructed opening to the adjoining room shall be at least 8 percent of the
floor area of the interior room or space, but not less than 25 square feet (2.33 m2). The
ventilation openings to the outdoors shall be based on a total floor area being ventilated.
403.2 BATHROOMS AND TOILET ROOMS. Every bathroom and toilet room shall
provide openable window or exhaust fan.
comply with the ventilation requirements for habitable spaces as required by Section
X
403. 1, except that a window shall not be required in such spaces equipped with a
mechanical ventilation system. Air exhausted by a mechanical ventilation system from a
bathroom or toilet room shall discharge to the outdoors and shall not be recirculated.
403.3 COOKING FACILITIES. Unless approved through the certificate of occupancy,
cooking shall not be permitted in any rooming unit or dormitory unit, and a cooking
facility or appliance shall not be permitted to be present in a rooming unit or dormitory
unit. Exception: Where specifically approved in writing by the code official.
403.4 PROCESS VENTILATION. Where injurious, toxic, irritating or noxious fumes,
gases, dusts or mists are generated, a local exhaust ventilation system shall be provided
to remove the contaminating agent at the source. Air shall be exhausted to the exterior
and not be recirculated to any space.
403.5 CLOTHES DRYER EXHAUST. Clothes dryer exhaust systems shall be
independent of all other systems and shall be exhausted in accordance with the
manufacturer's instructions.
Section 404 Occupancy Limitations
404.1 PRIVACY. Dwelling units, hotel units, housekeeping units, rooming units and
dormitory units shall be arranged to provide privacy and be separate from other
adjoining spaces.
404.2 MINIMUM ROOM WIDTHS. A habitable room, other than a kitchen, shall not
be less than 7 feet (2134 mm) in any plan dimension. Kitchens shall have a clear
passageway of not less than 3 feet (914 mm) between counterfronts and appliances or
counterfronts and walls.
404.3 MINIMUM CELING HEIGHTS. Habitable spaces, hallways, corridors, laundry
areas, bathrooms, toilet rooms and habitable basement areas shall have a clear ceiling
heights of not less than 7 feet (2134 mm). Exceptions: 1 & 2 family dwellings, beams or
girders spaced not less than 4 feet (1219 mm) on center and projecting not more than 6
inches (152 mm) below the required ceiling height. 2) Basement rooms in 1 & 2 family
dwellings occupied exclusively for laundry, study or recreation purposes, having a
ceiling height of not less than 6 feet 8 (2033) with not less than 6 feet 4 inches (1932
mm) of clear height under beams, girders, ducts and similar obstructions. 3) Rooms
occupied exclusively for sleeping, study or similar purposes and having a sloped ceiling
over all or part of the room, with a clear ceiling height of at least 7 feet (2134 mm) over
not less than 1/3 of the required minimum floor area. In calculating the floor area of such
rooms, only those portions of the floor area with a clear ceiling height of 5 feet (524
mm) or more shall be included.
404.4 BEDROOM REQUIREMENTS. Every bedroom shall comply with the
requirements of 404.4.1 through 404.4.5
404.4.1 AREA FOR SLEEPING PURPOSES. Every bedroom occupied by one person
shall contain at least 70 sq. ft. (6.5 m2) of floor area, and every bedroom occupied by
more than one person shall contain at least 50 sq. ft. (4.6m2) of floor area for each
occupant thereof.
404.4.2 ACCESS FOR BEDROOMS. Bedrooms shall not constitute the only means of
access to other bedrooms or habitable spaces and shall not serve as the only means of
egress from other habitable spaces. Exception: Units that contain fewer than two
bedrooms.
404.4.3 WATER CLOSET ACCESSIBILITY. Every bedroom shall have access to at
least one water closet and one lavatory without passing through another bedroom. Every
bedroom in a dwelling unit shall have access to at least one water closet or lavatory
located in the same story as the bedroom or an adjacent story.
404.4.4 PROHIBITED OCCUPANCY. Kitchens and nonhabitable spaces shall not be
used for sleeping purposes.
404.4.5 OTHER REQUIREMENTS. Bedrooms shall comply with the applicable
provisions of this code including, but not limited to, the light, ventilation, room area,
ceiling height and room width requirements of this chapter; the plumbing facilities and
water -heating facilities requirements of Chapter 5; the heating facilities and electrical
receptacle requirements for Chapter 6; and the smoke detector and emergency escape
requirement for Chapter 7.
404.5 OVERCROWDING. Dwelling units shall not be occupied by more occupants than
permitted by the minimum area requirements of Table 405.5.
1-2 Occupants 3-5 Occupants 6 or more Occupants
Living Room No Requirements 120 sq. ft. 150 sq. ft.
Dining Room No Requirements 80 sq. ft. 100 sq. ft.
Kitchen 50 sq. ft. 50 sq. ft. 60 sq. ft.
Bedroom - All shall comply with Section 405.3
404.5.1 SLEEPING AREA. The minimum occupancy area required by Table 404.5 shall
not be included as a sleeping area in determining the minimum occupancy area for
sleeping purposes. All sleeping areas shall comply with Section 404.4.
404.5.2 COMBINED SPACES. Combined living room and dining room spaces shall
comply with the requirements of Table 404.5 if the total area is equal to that required for
separate rooms and if the space is located so as to function as combination living
room/dining room.
404.6 EFFICIENCY UNIT. Nothing in this section shall prohibit an efficiency living
unit from meeting the following requirements. 1) A unit occupied by not more than two
occupants shall have a clear floor area of not less than 220 sq. ft. (20.4 m2). A unit
occupied by three occupants shall have a clear floor of not less than 320 sq. ft. (29.7
m2). These required areas shall be exclusive of the areas required by Items 2 and 3.2)
The unit shall be provided with a kitchen sink, cooking appliance and refrigeration
facilities, each having a clear working space of not less than 30 inches (762 mm) in
front. Light and ventilation conforming to this code shall be provided. 3) The unit shall
be provided with a separate bathroom containing a water closet, lavatory and bathtub or
shower. 4) The maximum number of occupants shall be three.
404.7 FOOD PREPARATION. All spaces to be occupied for food preparation purposes
Needs cleaning.
shall contain suitable space and equipment to store, prepare and serve foods in a sanitary
X
manner. There shall be adequate facilities and services for the sanitary disposal of food
wastes and refuse, including facilities for temporary storage.
Chapter 5 - Plumbing Facilities and Fixture Requirements
Section 502 Required Facilities
505.4 WATER HEATING FACILITIES. Water heating facilities shall be properly
Must have hot and cold water.
installed, maintained and capable of providing an adequate amount of water to be drawn
at every required sink, lavatory, bathtub, shower and laundry facility at a temperature of
not less than 100 degrees F (43 degrees C). A gas-buming water heater shall not be
X
located in any bathroom, toilet room, bedroom or other occupied room normally kept
closed, unless adequate combustion air is provided. An approved combination
temperature and pressure -relief valve and relief valve discharge pipe shall be properly
installed and maintained on water heaters.
506 Sanitary Drainage System
506.1 GENERAL. All plumbing fixtures shall be properly connected to either a public
sewer system or to an approved private sewage disposal system.
506.2 MAINTENANCE. Every plumbing stack, vent, waste and sewer line shall
function properly and be kept free from obstructions, leaks and defects.
Chapter 6 - Mechanical and Electrical Requirements
Section 602 Heating Facilities
602.1 FACILITIES REQUIRED. Heating facilities shall be provided in structures as
required by this section.
602.2 RESIDENTIAL OCCUPANCIES. Dwellings shall be provided with heating
facilities capable of maintaining a room temperature of 68 degrees F (20 degrees C) in
all habitable rooms, bathrooms and toilet rooms based on the winter outdoor design
temperature for the locality indicated in Appendix D of the International Plumbing
Code. Cooking appliances shall not be used to provide space heating to meet the
requirements of this section. Exception: In areas where the average monthly
temperature is above 30 degrees F (-1 degree C), a minimum temperature of 65 degrees
F (18 degrees C) shall be maintained.
602.3 HEAT SUPPLY. Every owner and operator of any building who rents, leases or
Heater needs repair -won't shut off.
lets one or more dwelling unit, rooming unit, dormitory or guestroom on terms, either
expressed or implied, to furnish heat to the occupants, thereof shall supply heat during
the period from October 1 to May 1 to maintain a temperature of not less than 68
degrees F (20 degrees C) in all habitable rooms, bathrooms and toilet rooms. Exception:
1) When the outdoor temperature is below the winter outdoor design temperature for the
X
locality, maintenance of the minimum room temperature shall not be required provided
that the heating system is operating at its full design capacity. The winter outdoor
design temperature for the locality shall be as indicated in Appendix D of the
International Plumbing Code. 2) In areas where the average monthly temperature is
above 30 degrees F (-1 degree C) a minimum temperature of 65 degrees F (18 degree C)
shall be maintained.
602.4 OCCUPIABLE WORK SPACES. Indoor occupiable work spaces shall be
supplied with heat during the period from October 1 to May 1 to maintain a temperature
of not less than 65 degrees F (18 degree C) during the period the spaces are occupied.
Exceptions: 1) Processing, storage and operation areas that require cooling or special
temperature conditions. 2) Areas in which persons are primarily engaged in vigorous
physical activities.
602.5 ROOM TEMPERATURE MEASUREMENT. The required room temperatures
shall be measured 3 feet (914 mm) above the floor near the center of the room and 2 feet
(6 10 mm) inward from the center of each exterior wall.
Section 603 Mechanical Equipment
603.1 MECHANICAL APPLIANCES. All mechanical appliances, fireplaces, solid fuel-
Hot water tank rotted out. B -vent rusty. Replace.
burning appliances, cooking appliances and water heating appliances shall be properly
X
installed and maintained in a safe working condition, and shall be capable of performing
the intended function.
603.2 REMOVAL OF COMBUSTION PRODUCTS. All fuel -burning equipment and
appliances shall be connected to an approved chimney or vent. Exception: Fuel -burning
equipment and appliances which are labeled for unvented operation.
603.3 CLEARANCES. All required clearances to combustible materials shall be
maintained.
603.4 SAFETY CONTROLS. All safety controls for fuel -burning equipment shall be
maintained in effective operation.
603.5 COMBUSTION AIR. A supply of air for complete combustion of the fuel and for
ventilation of the space containing the fuel -burning equipment shall be provided for the
fuel -burning equipment.
603.6 ENERGY CONSERVATION DEVICES. Devices intended to reduce fuel
consumption by attachment to a fuel -burning appliance, to the fuel supply line thereto,
or to the vent outlet or vent piping therefrom, shall not be installed unless labeled for
such purpose and the installation is specifically approved.
Section 604 Electrical Facilities
604.1 FACILITIES REQUIRED. Every occupied building shall be provided with an
electrical system in compliance with the requirements of this section and Section 605.
604.2 SERVICE. The size and usage of appliances and equipment shall serve as a basis
for determining the need for additional facilities in accordance with the ICC Electrical
Code. Dwelling units shall be served by a three-wire, 120/240 volt, single phase
electrical service having a rating of not less than 60 amperes.
604.3 ELECTRICAL SYSTEM HAZARDS. Where it is found that the electrical system
Receptacle covers missing.
in a structure constitutes a hazard to the occupants or the structure by reason of
X
inadequate service, improper fusing, insufficient receptacle and lighting outlets,
improper wiring or installation, deterioration or damage, or for similar reasons, the code
official shall require the defects to be corrected to eliminate the hazard.
Section 605 Electrical Equipment
605.1 INSTALLATION. All electrical equipment, wiring and appliances shall be
Has new electrical service-Show documentation of final
X
properly installed and maintained in a safe and approved manner.
inspection approval. Service panel needs breakers
labeled.
605.2 RECEPTACLES. Every habitable space in a dwelling shall contain at least two
separate and remote receptacle outlets. Every laundry area shall contain at least one
grounded-type receptacle or a receptacle with a ground fault circuit interrupter. Every
bathroom shall contain at least one receptacle. Any new bathroom receptacle outlet
shall have ground fault circuit interrupter protection.
605.3 LIGHTING FIXTURES. Every public hall, interior stairway, toilet room, kitchen,
bathroom, laundry room, boiler room, and furnace room shall contain at least one
electric lighting fixture.
Section 606 Elevators, Escalators and Dumbwaiters
606.1 GENERAL. Elevators, dumbwaiters and escalators shall be maintained to sustain
safely all imposed loads, to operate properly, and to be free from physical and fire
hazards. The most current certificate of inspection shall be on display at all times within
the elevator or attached to the escalator or dumbwaiter; or the certificate shall be
available for public inspection in the office of the building operator.
606.2 ELEVATORS. In buildings equipped with passenger elevators, at least one
elevator shall be maintained in operation at all times when the building is occupied.
Exception: Buildings equipped with only one elevator shall be permitted to have the
elevator temporarily out of service for testing or servicing.
607 Duct Systems
607.1 GENERAL. Duct systems shall be maintained free of obstructions and shall be
capable of performing the required function.
Chapter 7 Fire Safety Requirements
Section 702 Means of Egress
702.1 GENERAL A safe, continuous and unobstructed path of travel shall be provided
from any point in a building or structure to the public way. Means of egress shall
comply with the International Fire Code.
702.2 AISLES. The required width of aisles in accordance with the International Fire
Code shall be unobstructed.
702.3 LOCKE DOORS. All means of egress doors shall be readily openable from the
side from which egress is to be made without the need for keys, special knowledge or
effort, except where the door hardware conforms to that permitted by the International
Building Code.
702.4 EMERGENCY ESCAPE OPENINGS. Required emergency escape openings shall
be maintained in accordance with the code in effect at the time of construction, and the
following. Required emergency escape and rescue openings shall be operational from
the inside of the room without the use of keys or tools. Bars, grilles, grates or similar
devices are permitted to be placed over emergency escape and rescue openings provided
the minimum net clear opening size complies with the code that was in effect at the time
of construction and such devices shall be releasable or removable from the inside
without the use of a key, tool or force greater than that which is required for normal
operation of the escape and rescue opening.
Section 703 Fire Resistance Ratings
703.1 FIRE-RESISTANCE-RATED ASSEMBLIES. The required fire-resistance rating
of fire-resistance rated,walls, fire stops, shaft enclosures, partitions and floors shall be
maintained.
703.2 OPENING PROTECTIVES. Required opening protectives shall be maintained in
an operative condition. All fire and smokestop doors shall be maintained in operable
condition. Fire doors and smoke barrier doors shall not be blocked or obstructed or
otherwise made inoperable.
Section 704 Fire Protection Systems
704.1 GENERAL. All systems, devices and equipment to detect a fire, actuate an alarm
or suppress or control a fire or any combination thereof shall be maintained in an
operable condition at all times in accordance with the International Fire Code.
704.2 SMOKE ALARMS. Single or multiple -station smoke alarms shall be installed and
Install smoke alarms as per 704.2. Note: Basement will
maintained in Groups R-2, R-3, R-4 and in dwellings not regulated in Group R
need a smoke alarm.
occupancies, regardless of occupant load at all of the following locations: 1) On the
ceiling or wall outside of each separate sleeping area in the immediate vicinity of
bedrooms. 2) In each room used for sleeping purposes. 3) In each story within a
X
dwelling unit, including basements and cellars but not including crawl spaces and
uninhabitable attics. In dwellings or dwelling units with split levels and without an
intervening door between the adjacent levels, a smoke alarm installed on the upper level
shall suffice for the adjacent lower level provided that the lower level is less than one
full story below the upper level. Single or multiple station smoke alarms shall be
installed in other groups in accordance with the International Fire Code.
704.3 POWER SOURCE. In Group R occupancies and in dwellings not regulated as
Hardwire and interconnect.
Group R occupancies, single station smoke alarms shall receive their primary power
from the building wiring provided that such wiring is served from a commercial source
and shall be equipped with a battery backup. Smoke alarms shall emit a signal when the
batteries are low. Wiring shall be permanent and without a disconnecting switch other
than as required for overcurrent protection. Exception: Smoke alarms are permitted to
X
be solely battery operated in buildings where no construction is taking place, buildings
that are not served from a commercial power source and in existing areas of buildings
undergoing alterations or repairs that do not result in the removal of interior wall or
ceiling finishes exposing the structure, unless there is an attic, crawl space or basement
available which could provide access for building wiring without the removal of interior
finishes.
704.4 INTERCONNECTION. Where more than one smoke alarm is required to be
Interconnect.
installed within an individual dwelling unit in Group R-2, R-3, R-4 and in dwellings not
regulated as Group R occupancies, the smoke alarms shall be interconnected in such a
manner that the activation of one alarm will activate all of the alarms in the individual
unit. The alarm shall be clearly audible in all bedrooms over background noise levels
X
with all intervening doors closed. Exception: 1) Interconnection is not required in
buildings which are not undergoing alterations, repairs or construction of any kind. 2)
Smoke alarms in existing areas are not required to be interconnected where alterations or
repairs do not result in the removal of interior wall or ceiling finishes exposing the
structure, unless there is an attic, crawl space or basement available which could provide
access for interconnection without the removal of interior finishes.
CITY Of ])LAIQ 0 'k I'll I-„q� Vk5P � _0Soo
� rU� sig
0`�
November 19, 2010 Cn2 `21 �o� �ye c�
OWNER (S) OF RECORD: (As Identified from the Washington County Assessor's Office)
Henry R. Gregory Revocable Trust
2068 Nebraska St.
Blair, NE 68008
RE: Inspection Request for 2267 Nebraska Street, Blair, Nebraska
Lot 7 and Part of vacated Street, Block 4, Dexter's First Addition, Blair City,
Washington County, NE
Dear Mr. Gregory,
This is a courtesy notice informing you the City of Blair has received a complaint that your
property known as "2267 Nebraska Street, Lot 7 and Part of vacated Street, Block 4,
Dexter's First Addition, Blair City, Washington County, Nebraska” may be in violation of
the City's property maintenance code. The City enforces the 2009 International Property
Maintenance Code.
In order for the Building Inspector to make a formal evaluation of the property, please schedule
an inspection by Tuesday, November 30, 2010. After the inspection, you will receive a letter
outlining the violations that need to be corrected and a deadline for having them corrected. If no
violations are found, the city will issue you a letter to that effect.
To schedule an inspection, please contact Blair City Hall at (402) 426-4191, between 8:00 AM
and 4:30 PM, Monday through Friday. Your prompt attention to this matter is greatly
appreciated.
Sincerely,
Arendaeeler
City Clerk
Iz—
EQUAL SING
OPPORTUNITY
218 South 16th Street - Blair, Nebraska 68008 - 402-426-4191 - Fax 402-426-4195 - E-mail cityofblalr@cl,blair,ne.us