re-2011-00066_0002.jpg * * A CCESSIBILIT Y UPDA TE From: Plans Division This is to make all aware that Official State Interpretation 96 -05, dealing with the encroachment of the five -foot turning radius in a single user toilet shall be eliminated. SNAG requires a five -foot turning circle within a single user toilet. Section 4.22.2 states that the door shall not swing into the clear space of any fixture. The section does not restrict the door to swing into the turning circle. This will apply to both new and remodeled restrooms. The clear floor space for a lavatory, Title 156, 4.19.3 A clear floor space 30" x 48" complying with 4.2.3 shall be provided in front of a lavatory forward approach. Clear floor space may overlap accessible route and shall extend a maximum of 19" under the lavatory. The clear floor space for a water closet not located in a stall, Title 156, 4.16.2. As shown below. Space at least 60 inches wide is necessary for side transfers and when provided a 56 inch depth is permitted for either a forward or side approach because of the maneuvering space available beside the water closet. 60" LAIN. a�iHl� #0 AL19 5e" I.1 N. U . ti 03AI303b, _ 4 REQUIRED CRAB BARS NOT SHOWN 45" MIN. 48" MIN. I 56" MIN. _Y —LF REQUIRED GRAB BARS NOT SHOWN If the lavatory is located less than 42 inches from the toilet centerline, a side transfer is not possible. Clear floor space less than 60 inches wide is dimensioned in length specifically for diagonal or perpendicular transfers based on the approach.