Loading...
ad--2010-00079_0002.jpg VENTILATION TABLE 403.3- continued TABLE 403.3- continued • REQUIRED OUTDOOR VENTILATION AIR REQUIRED OUTDOOR VENTILATION AIR ESTIMATED ESTIMATED MAXIMUM OUTDOOR AIR MAXIMUM OUTDOOR AIR OCCUPANT (Cubic feet per OCCUPANT (Cubic feet per LOAD, PERSONS minute (cfm) LOAD, PERSONS minute (cfm) OCCUPANCY PER 1,000 per person) OCCUPANCY PER 1,000 per person) CLASSIFICATION SQUARE FEETa UNLESS NOTEDe CLASSIFICATION SQUARE FEETa UNLESS NOTED Private dwellings, single and Specialty shops - continued multiple 50 cfm intermittent or 20 Garages, common for - 1.5 cfm/ft2 cfm continuous multiple units Nail salon ' per station Garages, separate for - 100 cfm per car Pet Shops - 1.00 cfm/ft each dwelling Reducing salons 20 15 Kitchensg - 100 cfm intermittent or 25 Supermarkets 8 15 cfm continuous Sports and amusement Ballrooms and discos 100 25 Living areas` Based upon Bowling alleys (seating areas 70 25 number of 0.35 air changes g Y ( g ) bedrooms. fast per hour or 15 cfm Game rooms 70 25 2 bedroom: s. each per person, Ice arenas - 0.50 cfm/ft additional whichever is Playing floors (gymnasiums) 30 20 bedroom: 1 greater Spectator areas 150 15 Swimming pools (pool and deck ' Toilet rooms and - Mechanical area) 0.50 cfm/f bathroomsg• exhaust capacity of Storage 50 c in cfm Repair garages, enclosed or - parking garages 1.5 cfm/ft? continuous Warehouses - 0.05 cfm/ft Public spaces Theaters Corridors and utilities - 0.05 cfm/ft Auditoriums 150 15 • Elevator cars 1.00 cfm/ft Lobbies 150 20 Locker rooms 0.5 cfm1ft Stages, studios 70 15 Shower rooms 50 cfm Ticket booths 60 20 (per shower head)g• intermittent or 20 cfm continuous Transportation Smoking lounges 70 60 Platforms 100 15 Toilet roomsg 75 cfm per water Vehicles 150 15 Waiting rooms 100 15 closet or urinal Workrooms Retail stores, sales floors and Bank vaults 5 15 showroom floors Darkrooms - 0.50 cfm/ft Basement and street - 0.30 cfm/f2 Duplicating, printing - 0.50 cfm/f0 Dressing rooms - 0.20 cfm/ft' 2 Meat processing` 10 15 Malls and arcades - 0.20 cfm/ft Pharmacy 20 15 Shipping and receiving - 0.15 cfm/ft Photo studios 10 15 Smoking lounges 70 60 Storage rooms - 0.15 cfm/ft For SI: 1 cubic foot per minute = 0.0004719 m /s, l ton = 908 kg, Upper floors - 0.20 cfm/ft 1 cubic foot per minute per square foot = 0.00508 m /(s • m Warehouses - 0.05 cfm/ft2 °C = [(°F) - 321/1.8, 1 square foot = 0.0929 m a. Based upon net floor area. Specialty shops b. Mechanical exhaust required and the recirculation of air from such spaces as Automotive motor- permittedby Section403.2.1 isprohibited (see Section 403.2.1, Items 1 and 3). fuel- dispensing stations - 1.5 cfm/ft c. Spaces unheated or maintained below 50 °F are not covered by these require - Barber 25 15 ments unless the occupancy is continuous. Beauty 25 25 d. Ventilation systems in enclosed parking garages shall comply with Section ' Clothiers, furniture - 0.30 cfm1f1? 404. ' Embalm /ft Embalming room 2.0 cfm e. Where the ventilation rate is expressed in cfm/ft such rate is based upon Florists 8 15 cubic feet per minute per square foot of the floor area being ventilated. Hardware, drugs, fabrics 8 15 f. The sum of the outdoor and transfer air from adjacent spaces shall be suffi- cient to provide an exhaust rate of not less than 1.5 cfm/ft g. Transfer air permitted in accordance with Section 403.2.2. h. Mechanical exhaust is required and recirculation is prohibited except that recirculation shall be permitted where the resulting supply airstream con - (continued) sists of not more than 10 percent air recirculated from these spaces (see Sec- tion 403.2.1, Items 2 and 4). i. The required exhaust system shall capture the contaminants and odors at their source. 32 2006 INTERNATIONAL MECHANICAL CODE"