Loading...
re-2010-00202_0003 (2).jpg Chapter 3 — System Design Page 3 -14 REV, 2 PCI -35ABC with 4 nozzles CYLINDER / T1 F_ T2 NOZZLE D02664PC Cylinder Size Maximum Nozzle Type Piping Section Size Length Elbows ` Nozzle Quantity Maximum Maximum PCI -35ABC 4 Any Combination Cylinder to T1 1 in. 30 ft. (91 m) 7 of NV -P1 (see Note 5), NV -DP2, or NV -UF T1 to T2 1 in. 8 ft. (2,4 m) 2 T2 to Nozzle 3/4 in. 8 ft. (2.4 m) 4 PCI -35ABC 4 NV -UF or any Cylinder to T1 1 in. 30 ft. (9.1 m) 7 combination of NV -P1, NV -DP2, N -PLU T1 to T2 1 in. 8 ft. (2.4 m) 2 T2 to Nozzle 3/4 in. 8 ft. (2.4 m) 4 dfiEr 1. System piping must be balanced. Balanced piping is that in which the difference between the shortest actual pipe length from T1 to nozzle and the longest actual pipe length from T1 to nozzle does not exceed 10% of the longest actual pipe length from T1 to nozzle. T2 to nozzle on the same branch must not exceed 10% of each other. The number and type of fittings for all last tee to nozzle sections must be equal. 2. A Main /Reserve Swing Check Valve, Part No. 417788, may be located between the cylinder and Ti. 3. All systems protecting vehicle paint spray booths require a factory pre -set time delay. 4. When using an NV -P1 nozzle, the two largest discharge orifices in the nozzle body must be positioned parallel to the longest dimension of the hazard being protected. ► 5. Maximum height of nozzle from base of tank to nozzle — 20 ft. (6.1 m). ULEX 3437 CEx732 September 1, 2006