re-2010-00202_0001 (2).jpg Chapter 3 — System Design Page 3 -4 REV. 2 ►g. Nozzle Coverages Protection Nozzle Location Zone /Nozzle Specifications within Nozzle Nozzle Protection Nozzle L W Ht Maximum Protection Zone Offset Orientation A, Work Areal NV -WA See Table 3 -1 Volume 1920 cu. ft. 2 ft. maximum 0 to 6 in. Vertical Area 160 sq. ft. off center pointing down Diagonal 18.86 ft. (each side) Work Areal NV -SW See Table 3 -1A Volume 1920 cu. ft. 2 ft. maximum 0 to 6 in. Vertical Area 160 sq. ft, off center pointing down Diagonal 12.8 ft. (each side) (orifices in (to farthest corner) direction of arrow) Backdrafl NV -P1 4 fl. 14 ft. 12 ft. Volume 672 cu. ft. Shortest side - center 0 to 6 in. Vertical Plenum Area 56 sq. fl. Side 14 fl. Longest side -3 inch off center (each side) Pant Leg NV -P1 4 fl. 16 ft. 20 ft. Volume 1280 cu. ft. Shortest side- center o to 6 in. Vertical Plenum Area 64 sq. ft. Side 16 ft. Longest side -3 inch off center (each side) Pit NV -P1 24 ft 4 fl. 4 ft. Volume 384 cu. ft. Shortest side - center 0 to 6 in. Vertical (Option 1) Area 96 sq. ft. Side 24 ft. Longest side - center Pit NV -DP2 24 ft. 4 fl. 4 ft. Volume 384 cu. ft. Shortest side - center 2 to 8 in. Horizontal (Option 2) Area 96 sq. ft. Side 24 fl. Height- center Under Floor NV -UF 16 ft. 14 ft. 4 ft. Volume 896 cu. ft. Shortest side - center 0 to 6 in. Vertical Plenum Area 224 sq. ft. Side 16 ft. Longest side - center Exhaust NV -DP2 3 ft. 3 ft. 24 ft. Volume 216 cu. ft. Shortest side (cross 0 to 6 in. Horizontal for Duct Area 9 sq. ft. section) — center horizontal ducts Side 3 ft. Longest side (cross (Round Duct section) Vertical for 3 ft. 10 in. diameter) vertical ducts Exhaust N -DCT 12 ft. Perimeter or Length — center 0 to 6 in. Vertical Ducl 3 ft. 10 in. diameter Width — center (up) 24 ft. length I NV -WA and NV -SW nozzles can be used for plenum, pit, or under floor protection. The nozzle maximum specifications must be followed. 2 Pant leg dimensions 4 inch minimum x 48 inch maximum. 3 Nozzle offset is the maximum distance from the tip of the nozzle to the closest edge of the protection zone. Single nozzle application on a PCI -15ABC or two nozzle application on a PCI- 25sABC only. ► Note: If the exhaust duct is greater than 46 in. in diameter or 12 fl. perimeter, the use of total flood protection can be utilized. ULEX 3437 CEx732 September 1, 2006