Re: Novozymes Air Compressor Building plan review comments
Chris: Here's what we need to finish the review on the Air compressor Building:
1. Provide the HVAC General Design Notes sheet. It is missing from the set.
2. Show on the Special inspections notes that High Strength bolts are a required inspection.
3. Show the locations of portable fire extinguishers on the plans.
4. Provide energy calculations and show R- values of insulation.
5. Do the exterior lights provide at least one foot - candle of light for the exit discharge system?
Howard Wolfe