St Fire Marshal Code ReviewOmaha, NE 68137-
Your items have been reviewed for compliance with the Nebraska State Fire Marshal Act.
Shop Drawings - Fire Alarm System
REMARKS:
Review applies to the fire alarm system addition as shown only. The existing system shall comply with current code
requirements.
Occupancy Type — General Industrial Occupancy
Referenced — 2011 NFPA 70 / 2010 NFPA 72 / 2012 NFPA 90A / 2012 Life Safety Code (LSC)
Fire Protection Features Provided — Total Sprinkler & Fire Alarm
1. The required fire alarm system shall meet one of the following criteria:
(1) It shall provide occupant notification in accordance with 9.6.3.
(2) It shall sound an audible and visible signal in a constantly attended location for the purposes of initiating
emergency action.
LSC 40.3.4.3.1
Page 1 of 1
PLEASE CONTACT OFFICE INDICATED BELOW FOR A FINAL INSPECTION.
FINAL APPROVAL IS REQUIRED PRIOR TO OCCUPANCY OR USE
SIGNED:
Reviewed By: John Dodds Contact for Inspection: District A
246 S 14th St 246 S 14th St
Lincoln, NE 68508-1804 Lincoln, NE 68508-1804
john.dodds@nebraska.gov 402-471-2590
402-471-9465
NEBRASKA STATE FIRE MARSHAL
v PLANS DIVISION
U440
NFPWX Code Review
6/22/2023
1 Code Review Number: 06061-23
Submitting Party
Location
Steve Jensen
Novozymes Warehouse
I
General Fire and Safety
600 S 1 st St
13002 1 Street
Blair 68008
Omaha, NE 68137-
Your items have been reviewed for compliance with the Nebraska State Fire Marshal Act.
Shop Drawings - Fire Alarm System
REMARKS:
Review applies to a fire alarm system addition as shown only.
Occupancy Type - New General Industrial Occupancy
Referenced — 2011 NFPA 70 / 2010 NFPA 72 / 2012 NFPA 90A / 2012 Life Safety Code (LSC)
Fire Protection Features Provided — Total Sprinkler & Fire Alarm
NOTE: The permit and inspection of the branch circuit(s) supplying the fire alarm equipment(s) shall be completed by the
Nebraska State Electrical Division or their Delegated Authorities separate from this permit and inspection.
1. The branch circuit supplying the fire alarm equipment(s) shall supply no other loads. The location of the branch -circuit
overcurrent protective device shall be permanently identified at the fire alarm control unit. The circuit disconnecting
means shall have red identification, shall be accessible only to qualified personnel, and shall be identified as "FIRE
ALARM CIRCUIT." The red identification shall not damage the overcurrent protective devices or obscure the
manufacturer's markings. This branch circuit shall not be supplied through ground -fault circuit interrupters or arc -fault
circuit -interrupters. NFPA 70 760.41(B)
2. Where a required fire alarm system is out of service for more than 4 hours in a 24-hour period, the AHJ shall be notified,
and the building shall be evacuated OR an approved fire watch shall be provided for all parties left unprotected by the
shutdown until the fire alarm system has been returned to service. LSC 9.6.1.6
3. RE: NAC - In areas that are not continuously occupied automatic smoke detection shall be installed to provide
notification of fire at the following locations:
(1) Each fire alarm control unit.
(2) Notification appliance circuit power extenders.
(3) Supervising station transmitting equipment
LSC 9.6.1.8.1
Page I of l
PLEASE CONTACT OFFICE INDICATED BELOW FOR A FINAL INSPECTION.
FINAL APPROVAL IS REQUIRED PRIOR TO OCCUPANCY OR USE