St Fire Marshal Code Review�gTIFr� NEBRASKA STATE FIRE MARSHAL
L �� PLANS DIVISION
1
NFL►• - Code Review
8/17/2021
1 Code Review Number: 07126-21
Submitting Party
Location
Tim Mashek
Walmart #4568
Service First Fire Sprinkler
1882 Holly St
2212 East 39th Street North
Blair, NE 68008
Sioux Falls, SD 57104-
Your items have been reviewed for compliance with the Nebraska State Fire Marshal Act.
Shop Drawings -Sprinkler System
REMARKS:
Review applies to a sprinkler system remodel as shown only. The on -site inspector shall determine compliance of existing
conditions beyond the scope of this code review.
Occupancy Type - New Mercantile Occupancy
Codes Referenced - 2010 NFPA 13 / 2010 NFPA 24 / 2011 NFPA 25
Fire Protection Features Provided — Total Sprinkler
Construction Type - V (000)
1. Where a required fire protection system is out of service for more than 10 hours in a 24-hour period, the impairment
coordinator shall arrange for one of the following:
(a) Evacuation of the building or portion of the building affected by the system out of service.
(b) An approved fire watch.
(c) Establishment of a temporary water supply.
(d) Establishment and implementation of an approved program to eliminate potential ignition sources and limit the
amount of fuel available to the fire.
NFPA 25 15.5.2(4)
2. All piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at 200 psi
(13.8 bar) or 50 psi (3.5 bar) in excess of the system working pressure, whichever is greater, and shall maintain that
pressure without loss for 2 hours. NFPA 13 24.2.1
3. After the systems have been installed, the completed Contractor's Material and Test Certificates for Aboveground and
Underground piping shall be provided to and accepted by the State Fire Marshal to receive final approval. This must be
done before the system is put into service. Title 153 Chapter 19 003.05
4. In order for the State Fire Marshal's Office to create a record of each system for tracking purposes, every water -based
fire protection system shall have a separate and distinct serial identification number. Each system shall be tagged with
a seal issued by the State Fire Marshal's Office. The seal shall be placed in a highly visible location. Each of the
following devices must bear a separate identification tag and corresponding serial number. Title 153 chapter 19 003.07
(riser tags may be purchased at www.fscan.org)