ResCheck.tifREScheck Software Version 4.6.4
Compliance Certificate
Project Mark Bolander Residence
Energy Code:
2009 IECC
Location:
Blair, Nebraska
Construction Type:
Single-family
Project Type:
New Construction
Orientation:
Unspecified
Conditioned Floor Area:
5,053 ft2
Glazing Area
11%
Climate Zone:
5 (6506 HDD)
Permit Date:
9
Permit Number:
Construction Site:
Owner/Agent:
Valley Ridge Estates, Lot 4
Blair, NE
4860 Fixed: Wood Frame:Double Pane with Low -E
Designer/Contractor:
Randy Popken
Christensen Lumber
714 South Main
Fremont, NE 68025
(402)727-2211
randypopken@christensenlumber.c
om
o o e e
Compliance: 2.1% Better Than Code Maximum UA: 660 Your UA: 646
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum -code home.
Envelope Assemblies
Rear Walkout Wall: Wood Frame, 16" D.C.
378
21.0
0.0
0.057
16
Orientation: Back
3050-2W DH: Wood Frame:Double Pane with Low -E
30
0.310
9
Orientation: Unspecified
4860 Fixed: Wood Frame:Double Pane with Low -E
20
0.310
6
Orientation: Unspecified
4860 Fixed: Wood Frame:Double Pane with Low -E
20
0.310
6
Orientation: Unspecified
4860 Fixed: Wood Frame:Double Pane with Low -E
20
0.310
6
Orientation: Unspecified
Left Side Walkout Wall: Wood Frame, 16" o.c.
99
21.0
0.0
0.057
6
Orientation: Left side
Right Side Walkout Wall: Wood Frame, 16" D.C.
282
21.0
0.0
0.057
13
Orientation: Right side
3050r2W DH: Wood Frame:Double Pane with Low -E
30
0.310
9
Orientation: Unspecified
Patio Door: Glass
20
0.290
6
Orientation: Unspecified
Rear Foundation Wall: Solid Concrete or Masonry: interior Insulation
144
13.0
0.0
0.083
12
Orientation: Right side
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck Page 1 of 10
Right Foundation Wall: Solid Concrete or Masonry: interior Insulation
351
13.0 0.0
0.083
29
Orientation: Right side
Front Foundation Wall: Solid Concrete or Masonry: Interior Insulation
522
13.0 0.0
0.083
43
Orientation: Front
Left Foundation Wall: Solid Concrete or Masonry: interior Insulation
534
13.0 0.0
0.083
44
Orientation: Left side
Front Floor Rim: Wood Frame, 16" o.c.
59
21.0 0.0
0.057
3
Orientation: Front
Right Floor Rim: Wood Frame, 16" o.c.
70
21.0 0.0
0.057
4
Orientation: Right side
Rear Floor Rim: Wood Frame, 16" o.c.
59
21.0 0.0
0.057
3
Orientation: Back
Left Floor Rim: Wood Frame, 16" o.c.
70
21.0 0.0
0.057
4
Orientation: Left side
First Floor Front Wall: Wood Frame, 16" o.c.
568
21.0 0.0
0.057
26
Orientation: Front
2650-2W Fixed (Dining Room): Wood Frame:Double Pane with Low -E
25
0.310
8
Orientation: Unspecified
2650-2W Casement (Office): Wood Frame:Double Pane with Low -E
25
0.320
8
Orientation: Unspecified
Entry Door Sidelights: Wood Frame:Double Pane with Low -E
13
0.320
4
Orientation: Unspecified
Entry Door Transom: Wood Frame:Double Pane with Low -E
10
0.310
3
Orientation: Unspecified
Entry Door: Solid
20
0.140
3
Orientation: Unspecified
House/Garage Door: Solid
20
0.140
3
Orientation: Unspecified
First Floor Right Side Wall: Wood Frame, 16" o.c.
655
21.0 0.0
0.057
34
Orientation: Right side
3040 DH w/ 24" Transom (Powder Room): Wood Frame:Double Pane with Low-
18
0.310
6
E
Orientation: Unspecified
3050 DH (Eating Area): Wood Frame:Double Pane with Low -E
15
0.310
5
Orientation: Unspecified
Eating Area / Deck Door: Glass
20
0.290
6
Orientation: Unspecified
First Floor Rear Wall: Wood Frame, 16" o.c.
531
21.0 0.0
0.057
20
Orientation: Back
4050 Fixed w/ 24" Transom (Great Room): Wood Frame:Double Pane with Low-
28
0.310
9
E
Orientation: Unspecified
4050 Fixed w/ 24" Transom (Great Room): Wood Frame:Double Pane with Low-
28
0.310
9
E
Orientation: Unspecified
4050 Fixed w/ 24" Transom (Great Room): Wood Frame:Double Pane with Low-
28
0.310
9
E
Orientation: Unspecified
3050 Fixed (Eating Area): Wood Frame:Double Pane with Low -E
15
0.310
5
Orientation: Unspecified
3050 Fixed (Eating Area): Wood Frame:Double Pane with Law -E
15
0.310
5
Orientation: Unspecified
3050 Fixed (Eating Area): Wood Frame:Double Pane with Low -E
15
0.310
5
Orientation: Unspecified
3' Archtop (Eating Area): Wood Frame:Double Pane with Low -E
4
0.310
1
Orientation: Unspecified
3030 DH (Kitchen): Wood Frame:Double Pane with Low -E
9
0.310
3
Orientation: Unspecified
Project Title: Mark Bolander Residence
Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck
Page 2
of 10
2650 Fixed w/ Transom (Master Bedroom): Wood Frame:Double Pane with
18
0.310
6
Low -E
Orientation: Unspecified
2650 Fixed w/ Transom (Master Bedroom): Wood Frame:Double Pane with
18
0.310
6
Low -E
Orientation: Unspecified
First Floor Left Side Wall: Wood Frame, 16" o.c.
528
21.0 0.0
0.057
26
Orientation: Left side
3050 DH (Eating Area): Wood Frame:Double Pane with Low -E
15
0.310
5
Orientation: Unspecified
3050 DH (Master Bedroom): Wood Frame:Double Pane with Low -E
15
0.310
5
Orientation: Unspecified
3050 DH (Master Bedroom): Wood Frame:Double Pane with Low -E
15
0.310
5
Orientation: Unspecified
4848 Fixed (Bath #1): Wood Frame:Double Pane with Low -E
16
0.310
5
Orientation: Unspecified
2030 DH (Laundry): Wood Frame:Double Pane with Low -E
6
0.310
2
Orientation: Unspecified
Second Floor Front Rim: Wood Frame, 16" o.c.
49
21.0 0.0
0.057
3
Orientation: Front
Second Floor Right Side Rim: Wood Frame, 16" o.c.
35
21.0 0.0
0.057
2
Orientation: Right side
Second Floor Rear Rim: Wood Frame, 16" o.c.
49
21.0 0.0
0.057
3
Orientation: Back
Second Floor Left Side Rim: Wood Frame, 16" o.c.
35
21.0 0.0
0.057
2
Orientation: Left side
Second Floor Front Wall: Wood Frame, 16" o.c.
391
21.0 0.0
0.057
20
Orientation: Front
2650-2W Casement w/ Transom (Bedroom #2): Wood Frame:Double Pane with
35
0.320
11
Low -E
Orientation: Unspecified
Second Floor Right Side Wall: Wood Frame, 16" o.c.
280
21.0 0.0
0.057
16
Orientation: Right side
Second Floor Rear Wall: Wood Frame, 16" o.c.
391
21.0 0.0
0.057
13
Orientation: Back
4040 Fixed (Great Room Upper): Wood Frame:Double Pane with Low -E
46
0.310
14
Orientation: Unspecified
4040 Fixed (Great Room Upper): Wood Frame:Double Pane with Low -E
46
0.310
14
Orientation: Unspecified
4040 Fixed (Great Room Upper): Wood Frame:Double Pane with Low -E
46
0.310
14
Orientation: Unspecified
2640 Casement (Loft): Wood Frame:Double Pane with Low -E
10
0.320
3
Orientation: Unspecified
2640 Casement (Loft): Wood Frame:Double Pane with Low -E
10
0.320
3
Orientation: Unspecified
Second Floor Left Side Wall: Wood Frame, 16" o.c.
280
21.0 0.0
0.057
15
Orientation: Left side
2448-2W Casement (Bedroom #3): Wood Frame:Double Pane with Low -E
22
0.320
7
Orientation: Unspecified
Master Bedroom Cantilever: All -Wood Joist/Truss:Over Outside Air
11
21.0 0.0
0.044
0
Office Cantilever: All -Wood Joist/Truss:Over Outside Air
8
21.0 0.0
0.044
0
Dining Room Cantilever: All -Wood J oist/Truss: Over Outside Air
8
21.0 0.0
0.044
0
Powder Room Cantilever: All -Wood Joist/Truss:Over Outside Air
6
21.0 0.0
0.044
0
Kitchen Cantilever: All -Wood Joist/Truss:Over Outside Air
6
21.0 0.0
0.044
0
Bedroom #2 Cantilever: All -Wood J o ist/Truss: Over Outside Air
16
21.0 0.0
0.044
1
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck Page 3 of10
Bedroom #3 Over Garage: All -Wood joist/Truss:Over Unconditioned Space 71 21.0 0.0 0.044 3
Flat Ceiling: Flat Ceiling or Scissor Truss 1,841 21.0 29.0 0.020 37
Master Bedroom Cathedral Ceiling: Cathedral Ceiling 374 38.0 0.0 0.027 10
Eating Area Cathedral Ceiling: Cathedral Ceiling 156 38.0 0.0 0.027 4
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2009 IECC requirements in
REScheck Version 4.6.4 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name - Title Signature Date
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck Page 4 of 10
REScheck Software Version 4.6.4
Inspection Checklist
Energy Code: 2009 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
Pre-Inspection/Plan Review
Plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
& Req.ID
103.2
;Construction drawings and
;
❑Complies
[PR1]1
:documentation demonstrate
j ;❑Does
Not
;energy code compliance for the
i 3❑Not Observable
;building envelope.
i j❑Not Applicable
103.2,
;Construction drawings and
I
❑Complies
403.7
'documentation demonstrate
:❑Does
Not
[PR3]1
:energy code compliance for
❑Not Observable ;
;lighting and mechanical systems.
❑Not Applicable
'Systems serving multiple
;dwelling units must demonstrate
'
;compliance with the commercial
code.
j
403.6
:Heating and cooling equipment is;
Heating: Heating: ;❑Complies
[PR2]2
!sized per ACCA Manual S based
Btu/hr Btu/hr
❑Does Not
on loads per Manual j or
Cooling:Cooling:
❑Not Observable
other approved methods.
7
Btu/hr Btu/hr t❑Not
Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N 191620\Estimat! ng\REScheck.rck Page 5 of 10
303.2.1 A protective covering is installed to ;LJComplies
[FO11]2 :protect exposed exterior insulation ❑Does Not
and extends a minimum of 6 in. below ;❑Not Observable
;grade.
❑Not Applicable
403.8 ;Snow- and ice -melting system controls,LJComplies
[FO12]2 installed. ;❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
11 High Impact (Tier 1) ]-2-[-medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck Page 6 of 10
Section
# Framing / Rough -In Inspection
Plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
&'Req.ID'
402.1.1, Door U -factor. ; U- U- ;❑Complies ;See the Envelope Assemblies
402.3.4 :❑Does Not :table for values.
[FR1]1 ; ; I❑Not Observable
❑Not Applicable
402.1.1, ;Glazing U -factor (area -weighted U- U- ;❑Complies ;See the Envelope Assemblies
402.3.1, :average). :❑Does Not table for values.
402.3.3, '
❑Not Observable ;
[FR2]1 ;❑Not Applicable
1 I
I I I
I I I 1
303.1.3 IU -factors of fenestration products;
❑Complies
[FR4]1 are determined in accordance
1 1❑Does Not
U) ;with the NFRC test procedure or
I j❑Not Observable
;taken from the default table.
I ❑Not Applicable
402.4.4 ;Fenestration that is not site built
iDComplies
[FR20]1 is listed and labeled as meeting
AAMA/WDMA/CSA 101/I.S.2/A440
r +❑Does Not
I I
9 or has infiltration rates per NFRC
l❑Not Observable
3❑Not Applicable
,400 that do not exceed code
; limits.
4
I
402.4.5 IC -rated recessed lighting fixtures;
❑Complies ;
[FR16]2 Isealed at housing/interior finish
j❑Does Not
:and labeled to indicate 52.0 cfm
I❑Not Observable ;
leakage at 75 Pa.
❑Not Applicable
403.2.1 ;Supply ducts in attics are R- R- :"Complies ;
[FR12]1 insulated to >_R-8. All other ducts R- R- F❑Does Not
lin unconditioned spaces or I ❑Not Observable
,outside the building envelope are
linsulated to >_R-6. ;❑Not Applicable ;
403.2.2 ;All joints and seams of air ducts, 1
❑Complies
[FR13]1 lair handlers, filter boxes, and i
j❑Does
Not
;building cavities used as return I
❑Not Observable
;ducts are sealed.
j❑Not
Applicable
403.2.3 Building cavities are not used for
❑Complies
[FR15]3 ;supply ducts.
10Does
Not
jf
,� 1❑Not
Observable
{❑Not
Applicable
403.3 HVAC piping conveying fluids R- R- ;❑Complies
[FR17]2 !above 105 °F or chilled fluids :❑Does Not
(below 55 °F are insulated to >_R-
Q) ; ;❑Not Observable
3.
l :❑Not Applicable
403.4 ;Circulating service hot water R- R- j❑Complies
[FR18]2 'I pipes are insulated to R-2. ❑Does Not
;❑Not Observable '
:[:]Not Applicable
403.5 ;Automatic or gravity dampers are
;❑Complies ;
[FR19]2 Hnstalled on all outdoor air
❑Does Not
intakes and exhausts.
1❑Not Observable ;
I
l ❑Not Applicable ;
Additional Comments/Assumptions:
111 High Impact (Tier 1) 2 1 Medium Impact (Tier 2) 3 1 Low Impact (Tier 3)
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck Page 7 of 10
Section
#
Insulation Inspection
Plans Verified
Value
Field Verified
Value Complies?
Comments/Assumptions
&Req.113
303.1
;All installed insulation is labeled
❑Complies
[IN13]2
or the installed R-values
❑Does Not
`
provided.
;❑Not Observable
❑Not Applicable
402.1.1,
Floor insulation R-value.
R-
R-
;❑Complies ;See the Envelope Assemblies
402.2.5,
Wood ;
❑ Wood
:❑Does Not table for values.
402.2.6
[INl]l
❑ Steel
❑ Steel
:❑Not Observable
QV
❑Not Applicable
303.2,
Floor insulation installed per
❑Complies
402.2.6
manufacturer's instructions, and
€
❑Does Not
[IN2)1
:in substantial contact with the
;❑Not Observable
underside of the subfloor.
❑Not Applicable ;
402.1.1,
Wall insulation R-value. If this is a: R-
R-
;❑Complies ;See the Envelope Assemblies
402.2.4,
mass wall with at least 1/� of the:Wood
j
❑ Wood
;❑Does Not table for values.
402.2.5
[IN3]1
;wall insulation on the wall
;exterior, the exterior insulation
� E] Mass
❑ mass❑Not
Observable
:requirement applies.
I
1
1
I
I
E] Steel
i
i
I
I
1 I
❑Steel
;❑Not Applicable
1 I
,
1 I
I
1
303.2;Wall
insulation is installed per
❑Complies
[IN4]
manufacturer's instructions,
i
I❑Does Not
� t
❑Not Observable ,
;❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck Page 8 of 10
Section
#
Final Inspection Provisions
Plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
& Req.ID
402.1.1,
,Ceiling insulation R -value. Where R-
R-
;❑Complies ;See the Envelope Assemblies
402.2.1,
> R-30 is required, R-30 can be Wood
❑Wood
;❑Does Not ;table for values.
402.2.2
[FI1]1
;used if insulation is not ❑ Steel
;compressed at eaves. R-30 may
❑ Steel
;❑Not Observable
be used for 500 ftz or 20%
:❑Not Applicable
;(whichever is less) where
;
:sufficient space is not available.
;
303.1.1.1,
;Ceiling insulation installed per
3❑Complies
303.2
: manufacturer's instructions,
r❑Does
Not
[FI211
;Blown insulation marked every
:
;
3❑Not
Observable
-
;300 ftz.
;
❑Not Applicable
402.2.3
;Attic access hatch and door R-
R- I❑Complies
[FI3]1
:insulation zR-value of the
:❑Does
Not
:adjacent assembly.
;❑Not
Observable
j❑Not
Applicable
402.4.2,
;Building envelope tightness ACH 50 = ACH 50 = ;❑Complies
402.4.2.1
:verified by blower door test result
;❑Does
Not
[FI17]1
:of <7 ACH at 50 Pa. This
❑Not Observable ;
;requirement may instead be met
:via visual inspection, in which
;❑Not
Applicable
:case verification may need to
;occur during Insulation
Inspection.
403.2.2
; Post construction duct tightness cfm
cfm ;❑Complies
[FI4]1
test result of :58 cfm to outdoors,
❑Does Not
�)
or -512 cfm across systems. Or,
Observable ;
;rough -in test result of :56 cfm
_<
:across systems or 4 cfm :
,❑Not
;❑Not
Applicable ;
:without air handler. Rough -in test:
;verification may need to occur
:during Framing Inspection.
403.1.1
Programmable thermostats
inComplies
[Fl 9]2
( installed on forced air furnaces.
:❑Does
Not
aQ11
❑Not Observable ,
y
j❑Not
Applicable
403.1.2
Heat pump thermostat installed ;
;❑Complies
[F1 10]2
on heat pumps. I
❑Does Not
;&
;❑Not
;
Observable
j❑Not
Applicable
403.4
;Circulating service hot water i'
❑Complies
[Fl 11]2
:systems have automatic or {
❑Does Not
accessible manual controls.
;❑Not
Observable ;
j
j❑Not
Applicable
404.1
50% of lamps in permanent
❑Complies
[FI6]1
;fixtures are high efficacy lamps. ,
❑Does Not
j❑Not
Observable
j❑Not
Applicable
401.3
;Compliance certificate posted. ;
j❑Complies
[F17 ]2
j }
j❑Does
Not
f
;❑Not
Observable
I
UNot Applicable
303.3
;Manufacturer manuals for {
7❑Complies
[FI18]3
:mechanical and water heating i
?❑Does
Not
:equipment have been provided, 1
❑Not Observable
j❑Not Applicable
Additional Comments/Assumptions:
1 JHIgh Impact (Tier 1) 2 Medium Impact (Tier 2) 13'1 Low Impact (Tier 3)
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck Page 9 of 10
111 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Mark Bolander Residence Report date: 11/04/19
Data filename: P:\Projects\2019\N191620\Estimating\REScheck.rck Page 10 of10